The standard clarifier checks at once: detention time, surface overflow, weir overflow and solids loading, each compared with a typical range. Your numbers are worked through underneath.
Your numbers, step by step
- Flow to each of 2 units3.2 MGD ÷ 2 = 1.6 MGD
- Flow in gal/day1.6 × 1,000,000 = 1,600,000 gal/day
- Surface area0.785 × 60 ft × 60 ft = 2,826 ft²
- Volume2,826 ft² × 12 ft = 33,912 ft³ × 7.48 = 253,662 gal
- Flow per hour1,600,000 gal/day ÷ 24 = 66,667 gal/hr
- Detention time253,662 gal ÷ 66,667 gal/hr = 3.8 hours
- Surface overflow rate1,600,000 gal/day ÷ 2,826 ft² = 566 gpd/ft²
- Weir length, one peripheral weir3.14 × 60 ft = 188.4 ft
- Weir overflow rate1,600,000 gal/day ÷ 188.4 ft = 8,493 gpd/ft
- RAS to each of 2 units1.6 MGD ÷ 2 = 0.8 MGD
- Solids applied(1.6 + 0.8) MGD × 3,000 mg/L × 8.34 = 60,048 lb/day
- Solids loading rate60,048 lb/day ÷ 2,826 ft² = 21.2 lb/day/ft²
Why it works
A clarifier works when solids sink faster than the water carries them up and out. Each of these numbers measures one way the water can win that race. They all start with the flow reaching one tank, so total flow is split evenly across the units in service.
- Surface overflow rate is the gallons per day rising through each square foot of surface. It is really an upward speed: if the water climbs faster than a floc settles, the floc goes over the weir. That's why it's the number to watch in a storm.
- Weir overflow rate is the flow per foot of weir. Too much flow over too little weir speeds the water up near the launder and pulls light solids along with it.
- Solids loading rate is the pounds of solids each square foot has to settle and thicken each day. It uses plant flow plus RAS, because return sludge passes through the clarifier too. That's also why turning the RAS up raises it.
- Detention time is how long the average gallon stays in the tank: volume divided by flow. Too short and solids don't have time to settle. Too long in a primary and the sludge can go septic and float. The same math works for any tank, so the Detention tab covers aeration, chlorine contact and digesters too.
All four formulas are on the formula sheet.
Example: a storm with two clarifiers online
Two 60 ft secondary clarifiers, 12 ft deep, handle an average 3.2 MGD with 1.6 MGD of RAS at 3,000 mg/L MLSS. A storm pushes flow to 7.5 MGD and RAS stays where it is.
- 0.785 × 60 × 60 = 2,826 ft² of surface per clarifier
- 7.5 ÷ 2 = 3.75 MGD to each clarifier
- 3,750,000 ÷ 2,826 = 1,327 gpd/ft² surface overflow, above the usual ~1,200 peak limit
- 3,750,000 ÷ (3.14 × 60) = 19,904 gpd/ft over the weir
- (3.75 + 0.8) × 3,000 × 8.34 ÷ 2,826 = 40.3 lb/day/ft² of solids
- 253,662 gal ÷ 156,250 gal/hr = 1.62 hours detention
On an average day the same clarifiers run at 566 gpd/ft². At peak the surface overflow rate is the number out of line, so a third clarifier would help the most: 7.5 ÷ 3 = 2.5 MGD each, or 885 gpd/ft².
Do the numbers look reasonable?
These are broad textbook ranges for catching a typo or a units slip. Your plant's design basis and state standards are what count. The results above are checked against the same values.
| Number | Average flow | Peak flow | If it is far off |
|---|---|---|---|
| Surface overflow, primary | About 800–1,200 gpd/ft² | Up to about 3,000 | A radius entered as the diameter makes the area four times too small. |
| Surface overflow, secondary | About 400–800 gpd/ft² | Up to about 1,200 | Check the number of units. Total flow over one tank's area reads double with two online. |
| Weir overflow | Up to about 10,000 gpd/ft | Up to about 30,000 | A double-sided launder has twice the weir length. |
| Solids loading, secondary | About 20–30 lb/day/ft² | Up to about 50 | Leaving out the RAS flow makes it read low. |
| Detention, clarifiers | Primary about 1.5–2.5 hours, secondary about 2–4 | Shorter. Watch the rates instead | Gallons need the 7.48 conversion from cubic feet. |
| Detention, aeration | About 4–8 hours conventional, 18–36 extended | — | Use influent flow, not influent plus RAS, unless your SOP says otherwise. |
| Detention, chlorine contact | At least about 30 minutes | At least about 15 minutes | Your permit's contact time rules. Short-circuiting means the real time is shorter than the math. |
| Detention, anaerobic digester | About 15–30 days | — | Use the sludge feed rate in gal/day, and the active volume, not the full tank. |
Before you change anything
- Count only what's online. A clarifier drained for maintenance doesn't share the load. Neither does one with a broken drive.
- Check the split. The math assumes flow divides evenly. If one unit gets more, its rates are higher than these.
- Match the flow to the question. Use the day's average for routine checks and the peak hour when you're asking whether solids will wash out.
- Look at the blanket. A rising sludge blanket tells you more than any single rate. Measure it before and after a change.
- Level weirs. An uneven weir sends most of the flow over the low side, so the real weir rate there is higher than the average.
This is a study and planning aid. Your plant's SOPs, permit and process engineer take priority over any number on this page.